Specifications
AC-90
Type AC Cable
HCF-90
Type AC Cable
MC Cable
Type MC Cable
MC/IG
Type MC Cable
UL Manuafcturing Standard UL 4 UL 4 UL 1569 UL 1569
NEC Reference(s) 333 333, 517, 645 334, 501, 502, 503, 518, 520, 530 250-91, 334, 501, 502, 503, 517*, 518, 520, 530, 645
Circuit Conductors 2-4 2-4+ground 2 or more + ground 2 or more + 2 grounds
Insulated Bushings Required Required Recommended Recommended
Grounding Components Equipment: Bond Wire/Armor Combination Equipment: Bond Wire/Armor Combination plus Redundant/ Isolated: 1 insulated green conductor Equipment: 1 insulated green conductor in combination with armor Redundant/ Isolated: Additional green insulated conductor w/yellow stripe

* With prior approval of authority having jurisdiction only.